Trace heating

Electric heat tracing, heat tape or surface heating, is a system used to maintain or raise the temperature of pipes and vessels using heat tracing cables. Trace heating takes the form of an electrical heating element run in physical contact along the length of a pipe. The pipe is usually covered with thermal insulation to retain heat losses from the pipe. Heat generated by the element then maintains the temperature of the pipe. Trace heating may be used to protect pipes from freezing, to maintain a constant flow temperature in hot water systems, or to maintain process temperatures for piping that must transport substances that solidify at ambient temperatures. Electric trace heating cables are an alternative to steam trace heating where steam is unavailable or unwanted.[2]

Self-regulating heat tracing tape with the gray end seal next to a copper drain pipe with insulator wrapped around them. This protects the pipe from freezing.[1]

Development

Electric trace heating began in the 1930s but initially no dedicated equipment was available. Mineral insulated cables ran at high current densities to produce heat, and control equipment was adapted from other applications.[3] Mineral-insulated resistance heating cable was introduced in the 1950s, and parallel-type heating cables that could be cut to length in the field became available. Self-limiting thermoplastic cables were marketed in 1971.[4]

Control systems for trace heating systems developed from capillary filled-bulb thermostats and contactors in the 1970s to networked computerized controls in the 1990s, in large systems that require centralized control and monitoring.[5]

One paper projected that between 2000 and 2010 trace heating would account for 100 megawatts of connected load, and that trace heating and insulation would account for up to CAD $700 million capital investment in the Alberta oil sands.[6]

International standards applied in the design and installation of electric trace heating systems include IEEE standards 515 and 622, British standard BS 6351, and IEC standard 60208.[5]

Uses

The most common pipe trace heating applications include:

  • Freeze protection
  • Temperature maintenance
  • Snow Melting On Driveways

Other uses of trace heating cables include:

  • Ramp and stair snow / ice protection
  • Gulley and roof snow / ice protection
  • Underfloor heating
  • Door / frame interface ice protection
  • Window de-misting
  • Anti-condensation
  • Pond freeze protection
  • Soil warming
  • Preventing cavitation
  • Reducing Condensation On Windows

Freeze protection

Every pipe or vessel is subject to heat loss when its temperature is greater than ambient temperature. Thermal insulation reduces the rate of heat loss but does not eliminate it. Trace heating maintains the temperature above freezing by balancing heat lost with heat supplied. Normally, a thermostat is used to energise when it measures temperature falling below a set temperature value - usually between 3 °C and 5 °C and often referred to as the 'setpoint'. The thermostat will de-energise the trace heating when it measures temperature rising past another set temperature value - usually 2 °C higher than the setpoint value.

Gutter and roof de-icing

Placement of heat trace cable on roofs or in gutters to melt ice during winter months. When used in gutters the cable is not meant to keep the gutters free of ice or snow, but only to provide a free path for the melted water to get off the roof and down the downspout or drain piping.

Temperature maintenance

Hot water service piping can also be traced, so that a circulating system is not needed to provide hot water at outlets. The combination of trace heating and the correct thermal insulation for the operating ambient temperature maintains a thermal balance where the heat output from the trace heating matches the heat loss from the pipe. Self-limiting or regulating heating tapes have been developed and are very successful in this application.

A similar principle can be applied to process piping carrying fluids which may congeal at low temperatures, for example, tars or molten sulfur. Hit-temperature trace heating elements can prevent blockage of pipes.

Industrial applications for trace heating range from chemical industry, oil refineries, nuclear power plants, food factories. For example, wax is a material which starts to solidify below 70 °C which is usually far above the temperature of the surrounding air. Therefore, the pipeline must be provided with an external source of heat to prevent the pipe and the material inside it from cooling down. Trace heating can also be done with steam, but this requires a source of steam and may be inconvenient to install and operate.

In laboratories, researchers working in the field of materials science use trace heating to heat a sample isotropically. They may use trace heating in conjunction with a variac, so as to control the heat energy delivered. This is an effective means of slowly heating an object to measure thermodynamic properties such as thermal expansion.

Anti-cavitation purpose

As heating a thick fluid decreases its viscosity, it reduces losses occurring in a pipe. Therefore, the net positive suction head (pressure difference) available can be raised, decreasing the likelihood of cavitation when pumping. However, care must be taken not to increase the vapour pressure of the fluid too much, as this would have a strong side effect on the available head, possibly outweighing any benefit.[7]

Types

Constant electric power "series"

A series heating cable is made of a run of high-resistance wire, insulated and often enclosed in a protective jacket. It is powered at a specific voltage and the resistance heat of the wire creates heat. The downside of these types of heaters is that if they are crossed over themselves they can overheat and burn out, they are provided in specific lengths and cannot be shortened in the field, also, a break anywhere along the line will result in a failure of the entire cable. The upside is that they are typically inexpensive (if plastic style heaters) or, as is true with mineral insulated heating cables, they can be exposed to very high temperatures. Mineral insulated heating cables are good for maintaining high temperatures on process lines or maintaining lower temperatures on lines which can get extremely hot such as high temperature steam lines.

[2]

Typically series elements are used on long pipe line process heating, for example long oil pipe lines and quay side of load pipes on oil refineries.

Constant wattage

A constant wattage cable is composed of multiple constant electric power zones and is made by wrapping a fine heating element around two insulated parallel bus wires, then on alternating sides of the conductors a notch is made in the insulation. The heating element is then normally soldered to the exposed conductor wire which creates a small heating circuit; this is then repeated along the length of the cable. There is then an inner jacket which separates the bus wires from the grounding braid. In commercial and industrial cables, an additional outer jacket of rubber or Teflon is applied.[2]

The benefits of this system over series elements is that should one small element fail then the rest of the system will continue to operate, on the other hand damaged sections of cable (usually 3 ft span) will stay cold and possibly lead to freeze ups on said section. Also, this cable can be cut-to-length in-field due to its parallel circuitry, however, due to the circuit only running to the last zone on the cable, when installing on site you normally have to install slightly beyond the end of the pipe work. When installing constant wattage, or any heat tracing cable, it is important to not overlap or touch the cable to itself as it will be subject to overheating and burnout. Constant wattage cable is always installed with a thermostat to control the power output of the cable, making it a very reliable heating source.

The disadvantage of this cable is that most constant wattage cables do not have soldered connections to the bus wires but press on type contact and are therefore more prone to have cold circuits due to loose connections caused by cable manipulation and installation.

Self regulating

Self-regulating heat tracing tapes are cables whose resistance varies with temperature - low resistance for temperatures below the cable set point and high resistance for temperatures above the cable set point. When the cable temperature reaches the set point, the resistance reaches a high point, resulting in no more heat being supplied.

These cables use two parallel bus wires which carry electricity but do not create significant heat. They are encased in a semi-conductive polymer. This polymer is loaded with carbon; as the polymer element heats, it allows less current to flow so the cable is inherently power saving and only delivering heat and power where and when required by the system. The cables are manufactured and then irradiated and by varying both the carbon content and the dosage then different tape with different output characteristics can be produced. The benefits of this cable are the ability to cut to length in the field. It is more rugged, and much more reliable than a constant wattage cable; it cannot over-heat itself so it can be crossed over, but it is bad practice to install tape in this way. Self-regulating and constant wattage heating cables have specific maximum exposure temperature, which means that if they are subject to high temperatures then the tape can be damaged beyond repair. Also self-limiting tapes are subject to higher inrush currents on cold starting up similar to an induction motor, so a higher rated contactor is required.

Power supply and control

Trace heat cables may be connected to single-phase or (in groups) to three-phase power supplies. Power is controlled either by a contactor or a solid-state controller. For self-regulating cable, the supply must furnish a large warm-up current if the system is switched on from a cold starting condition. The contactor or controller may include a thermostat if accurate temperature maintenance is required, or may just shut off a freeze-protection system in mild weather.

Electrical heat tracing systems may be required to have earth leakage (ground fault or RCD) devices for personnel and equipment protection. The system design must minimize leakage current to prevent nuisance tripping; this may limit the length of any individual heating circuit.

Control system

The three phase systems are fed via contactors similar to a three phase motor 'direct on line' starter which is controlled by a thermostat somewhere in the line. This ensures that the temperature is kept constant and the line does not overheat or underheat.

If a line becomes frozen because the heating was switched off then this may take some time to thaw out using trace heating. This thawing out is done on the three phase systems by using an 'auto transformer' to give a higher voltage, and consequently higher current, and make the trace heating elements a bit hotter. The boost system is usually on a timer and switches back to 'normal' after a period of time.

References

  1. Raychem XL-Trace System: Installation and Operation Manual for Pipe Freeze Protection and Flow Maintenance (PDF). Pentair. March 2013. Archived from the original (PDF) on 9 July 2014. Retrieved 3 August 2014.
  2. Paul R. Smith, ed. Facilities engineering and management handbook : commercial, industrial, and institutional buildings,McGraw Hill,2001 ISBN 0-07-059323-X chapter 5 pages 5-198 through 5-201
  3. James Bilbro et al, Electric trace heating -state of the art, Paper 69 TP 20-IGA,IEEE TRANSACTIONS ON INDUSTRY AND GENERAL APPLICATIONS, JULY/AUGUST 1969 pages 476-480
  4. Ted Hammack and Stephen Kucklinca, Self-Limiting Electrical Heat Tracing:New Solution to Old Problems , IEEE Transactions on Industry Applications March/April 1977
  5. Chet Sandberg et al, Electrical Heat Tracing:International Harmonization Now and in the Future, IEEE Industry Standards Magazine, May/June 2002 pages 50-56
  6. Derek Brooks et al., Reducing the total Cost of Ownership of Electric Heat Tracing Systems in Northern Alberta
  7. "NPSH simplified" (PDF). Viking Pumps. Retrieved 15 April 2012.

Further reading

This article is issued from Wikipedia. The text is licensed under Creative Commons - Attribution - Sharealike. Additional terms may apply for the media files.