Power cable
A power cable is an electrical cable, an assembly of one or more electrical conductors, usually held together with an overall sheath. The assembly is used for transmission of electrical power. Power cables may be installed as permanent wiring within buildings, buried in the ground, run overhead, or exposed. Power cables that are bundled inside thermoplastic sheathing and that are intended to be run inside a building are known as NM-B (nonmetallic sheathed building cable).
Flexible power cables are used for portable devices, mobile tools, and machinery.
History
The first power distribution system developed by Thomas Edison in 1882 in New York City used copper rods, wrapped in jute and placed in rigid pipes filled with a bituminous compound.[1] Although vulcanized rubber had been patented by Charles Goodyear in 1844, it was not applied to cable insulation until the 1880s, when it was used for lighting circuits.[2] Rubber-insulated cable was used for 11,000-volt circuits in 1897 installed for the Niagara Falls power project.
Mass-impregnated paper-insulated medium voltage cables were commercially practical by 1895. During World War II several varieties of synthetic rubber and polyethylene insulation were applied to cables.[3]
Typical residential and office construction in North America has gone through several technologies:
- Early bare and cloth-covered wires installed with staples
- Knob and tube wiring, 1880s-1930s, using asphalt-saturated cloth or later rubber insulation
- Armored cable, known by the genericized trademark "BX" - flexible steel sheath with two cloth-covered, rubber-insulated conductors[4] - introduced in 1906 but more expensive than open single conductors
- Rubber-insulated wires with jackets of woven cotton cloth (usually impregnated with tar), waxed paper filler - introduced in 1922
- Modern two or three-wire+ground PVC-insulated cable (e.g., NM-B), produced by such brands as Romex®
- Aluminum wire was used in the 1960s and 1970s as a cheap replacement for copper and is still used today, but this is now considered unsafe, without proper installation, due to corrosion, softness and creeping of connection.[5]
- Asbestos was used as an Insulator (electricity) in some cloth wires from the 1920s to 1970s, but discontinued due to its health risk.
- Teck cable, a PVC-sheathed armored cable
Construction
Modern power cables come in a variety of sizes, materials, and types, each particularly adapted to its uses.[6] Large single insulated conductors are also sometimes called power cables in the industry.[7]
Cables consist of three major components: conductors, insulation, protective jacket. The makeup of individual cables varies according to application. The construction and material are determined by three main factors:
- Working voltage, determining the thickness of the insulation;
- Current-carrying capacity, determining the cross-sectional size of the conductor(s);
- Environmental conditions such as temperature, water, chemical or sunlight exposure, and mechanical impact, determining the form and composition of the outer cable jacket.
Cables for direct burial or for exposed installations may also include metal armor in the form of wires spiraled around the cable, or a corrugated tape wrapped around it. The armor may be made of steel or aluminum, and although connected to earth ground is not intended to carry current during normal operation. Electrical power cables are sometimes installed in raceways, including electrical conduit and cable trays, which may contain one or more conductors. When it is intended to be used inside a building, nonmetallic sheathed building cable (NM-B) consists of two or more wire conductors (plus a grounding conductor) enclosed inside a thermoplastic insulation sheath that is heat-resistant. It has advantages over armored building cable because it's lighter, easier to handle, and its sheathing is easier to work with.[8]
Power cables use stranded copper or aluminum conductors, although small power cables may use solid conductors in sizes of up to 1/0. (For a detailed discussion on copper cables, see: Copper wire and cable.). The cable may include uninsulated conductors used for the circuit neutral or for ground (earth) connection. The grounding conductor connects the equipment's enclosure/chassis to ground for protection from electric shock. These uninsulated versions are known are bare conductors or tinned bare conductors. The overall assembly may be round or flat. Non-conducting filler strands may be added to the assembly to maintain its shape. Filler materials can be made in non-hydroscopic versions if required for the application.
Special purpose power cables for overhead applications are often bound to a high strength alloy, ACSR, or alumoweld messenger. This cable is called aerial cable or pre-assembled aerial cable (PAC). PAC can be ordered unjacketed, however, this is less common in recent years due to the low added cost of supplying a polymeric jacket. For vertical applications the cable may include armor wires on top of the jacket, steel or Kevlar. The armor wires are attached to supporting plates periodically to help support the weight of the cable. A supporting plate may be included on each floor of the building, tower, or structure. This cable would be called an armored riser cable. For shorter vertical transitions (perhaps 30–150 feet) an unarmored cable can be used in conjunction with basket (Kellum) grips or even specially designed duct plugs.
Material specification for the cable's jacket will often consider resistance to water, oil, sunlight, underground conditions, chemical vapors, impact, fire, or high temperatures. In nuclear industry applications the cable may have special requirements for ionizing radiation resistance. Cable materials for a transit application may be specified not to produce large amounts of smoke if burned (low smoke zero halogen). Cables intended for direct burial must consider damage from backfill or dig-ins. HDPE or polypropylene jackets are common for this use. Cables intended for subway (underground vaults) may consider oil, fire resistance, or low smoke as a priority. Few cables these days still employ an overall lead sheath. However, some utilities may still install paper insulated lead covered cable in distribution circuits. Transmission or submarine cables are more likely to use lead sheaths. However, lead is in decline and few manufacturers exist today to produce such items. When cables must run where exposed to mechanical damage (industrial sites), they may be protected with flexible steel tape or wire armor, which may also be covered by a water-resistant jacket.
A hybrid cable can include conductors for control signals or may also include optical fibers for data.
Higher voltages
For circuits operating at or above 2,000 volts between conductors, a conductive shield will surround the conductor's insulation. This equalizes electrical stress on the cable insulation. This technique was patented by Martin Hochstadter in 1916;[9] the shield is sometimes called a Hochstadter shield. Aside from the semi conductive ("semicon") insulation shield, there will also be a conductor shield. The conductor shield may be semi conductive or non conducting. Only one cable company produces non conductive conductor shields though. The purpose of the conductor shield is similar to the insulation shield: it is a void filler and voltage stress equalizer.
To drain off stray voltage, a metallic shield will be placed over the "semicon." This shield is intended to "make safe" the cable by pulling the voltage on the outside of the insulation down to zero (or at least under the OSHA limit of 50 volts). This metallic shield can consist of a thin copper tape, concentric drain wires, flat straps, lead sheath, or other designs. The metallic shields of a cable are connected to earth ground at the ends of the cable, and possibly locations along the length if voltage rise during faults would be dangerous. Multi-point grounding is the most common way to ground the cable's shield. Some special applications require shield breaks to limit circulating currents during the normal operations of the circuit. Circuits with shield breaks could be single or multi point grounded. Special engineering situations may require cross bonding.
Liquid or gas filled cables are still employed in distribution and transmission systems today. Cables of 10 kV or higher may be insulated with oil and paper, and are run in a rigid steel pipe, semi-rigid aluminum or lead sheath. For higher voltages the oil may be kept under pressure to prevent formation of voids that would allow partial discharges within the cable insulation.
Liquid filled cables are known for extremely long service lives with little to no outages. Unfortunately, oil leaks into soil and bodies of water are of grave concern and maintaining a fleet of the needed pumping stations is a boon on the O+M budget of most power utilities. Pipe type cables are often converted to solid insulation circuit at the end of their service life despite a shorter expected service life.
Modern high-voltage cables use polyethylene or other polymers, including XLPE for insulation. They require special techniques for jointing and terminating, see High-voltage cable.
Flexibility of cables (stranding class)
All electrical cables are somewhat flexible, allowing them to be shipped to installation sites wound on reels, drums or hand coils. Flexibility is an important factor in determining the appropriate stranding class of the cable as it directly affects the minimum bending radius. Power cables are generally stranding class A, B, or C. These classes allow for the cable to be trained into a final installed position where the cable will generally not be disturbed. Class A, B, and C offer more durability, especially when pulling cable, and are generally cheaper. Power utilities generally order Class B stranded wire for primary and secondary voltage applications. At times, a solid conductor medium voltage cable can be used when flexibility is not a concern but low cost and water blocking are prioritized.
Applications requiring a cable to be moved repeatedly, such as for portable equipment, more flexible cables called "cords" or "flex" are used (stranding class G-M). Flexible cords contain fine stranded conductors, rope lay or bunch stranded. They feature overall jackets with appropriate amounts of filler materials to improve their flexibility, trainability, and durability. Heavy duty flexible power cords such as those feeding a mine face cutting machine are carefully engineered — their life is measured in weeks. Very flexible power cables are used in automated machinery, robotics, and machine tools. See power cord and extension cable for further description of flexible power cables. Other types of flexible cable include twisted pair, extensible, coaxial, shielded, and communication cable.
An X-ray cable is a special type of flexible high-voltage cable.
See also
- AC power plugs and sockets
- American wire gauge – for a table of cross section sizes
- Ampacity – for a description of current carrying capacity of wires and cables
- Cross-linked polyethylene
- Electrical cable
- Ethylene propylene rubber (EPR)
- Industrial and multiphase power plugs and sockets
- Overhead power line
- Portable cord
- Railway electrification system
- Restriction of Hazardous Substances Directive
- Voltage drop – another consideration when selecting proper cable sizes
References
- "undergrounding electric lines" A J Pansini, ISBN 0-8104-0827-9, 1978
- Underground Systems Reference Book, Edison Electric Institute, New York, 1957, no ISBN
- R. M. Black The History of Electric Wires and Cables, Peter Pergrinus, London 1983 ISBN 0-86341-001-4
- "10 Wiring Problems Solved | Electrical | Plumbing, HVAC & Electrical | This Old House - 12". Archived from the original on 2014-10-06. Retrieved 2014-10-03.
- "The True Story Behind Aluminum Wiring – Part One". 21 March 2015.
- Terrell Croft and Wilford Summers (ed), American Electricans' Handbook, Eleventh Edition, McGraw Hill, New York (1987) ISBN 0-07-013932-6, sections 2-13 through 2-84
- Donald G. Fink and H. Wayne Beaty, Standard Handbook for Electrical Engineers, Eleventh Edition, McGraw-Hill, New York, 1978, ISBN 0-07-020974-X pg. 18-85
- "Nonmetallic Building Cable". Granger. Retrieved 11 September 2020.
- Underground Systems