Self-contained breathing apparatus
A self-contained breathing apparatus (SCBA) is a device worn to provide an autonomous supply of breathable gas in an atmosphere that is immediately dangerous to life or health. They are typically used in firefighting and industry. The term self-contained means that the SCBA is not dependent on a remote supply of breathing gas (e.g., through a long hose). If designed for use under water, it is also known as a scuba set (self-contained underwater breathing apparatus). When not used underwater, they are sometimes called industrial breathing sets. Some types are also referred to as a compressed air breathing apparatus (CABA) or simply breathing apparatus (BA). Unofficial names include air pack, air tank, oxygen cylinder or simply pack, which are mostly used in firefighting.
An open circuit SCBA typically has three main components: a high-pressure gas storage cylinder, (e.g., 2,216 to 5,500 psi (15,280 to 37,920 kPa), about 150 to 374 atmospheres), a pressure regulator, and a respiratory interface, which may be a mouthpiece, half mask or full-face mask, assembled and mounted on a framed carrying harness.[1]
A self-contained breathing apparatus may fall into one of two categories: open-circuit or closed-circuit.[2]
Types
Closed-circuit
The closed-circuit type, also known as a rebreather, operates by filtering, supplementing, and recirculating exhaled gas. It is used when a longer-duration supply of breathing gas is needed, such as in mine rescue and in long tunnels, and going through passages too narrow for a big open-circuit air cylinder. Before open-circuit SCBA's were developed, most industrial breathing sets were rebreathers, such as the Siebe Gorman Proto, Siebe Gorman Savox, or Siebe Gorman Salvus. An example of modern rebreather SCBAs would be the SEFA.
Open-circuit
Open-circuit industrial breathing sets are filled with filtered, compressed air. Typical open-circuit systems have two stage regulators. The first stage reduces the pressure from storage pressure of up to more than 300 bar to about 10 bar for supply to the second stage on the mask, which further reduces it to just above atmospheric pressure via a demand valve when the pressure drops on inhalation. A positive pressure mask has the demand valve set to close when the pressure inside the mask is slightly above the external ambient pressure, so when the mask is removed from the face or leaks around the skirt, the demand valve will free-flow.
An open-circuit rescue or firefighting SCBA has a full-face mask, also called the face-piece, a demand regulator, air cylinder, pressure gauge, (sometimes with an integrated PASS device), and a harness with adjustable shoulder straps and waist belt which lets it be worn on the back. The air cylinder is commonly 4 liter, 6 liter, or 6.8 liter, but other sizes are also available. The endurance of the cylinder can be calculated from the volume, pressure and breathing rate of the user. The formula: volume (in liters) × pressure (in bars) / 40 (litres per minute) - 10 minutes (the 10 minutes is a safety margin, or reserve), so a 6-liter cylinder, of 300 bar, is 6 × 300 / 40 - 10 = 35 minutes working duration. The fitness and level of exertion of the wearer affect breathing rate, and result in variations of the actual usable time of the SCBA.
Air cylinders are made of aluminium, steel, or of a composite construction (usually glass or carbon-fiber wrapped.) The composite cylinders are the lightest in weight and are therefore preferred by fire departments (UK: fire and rescue services previously called fire brigades), but they also have the shortest lifespan and must be taken out of service after 15 years. Air cylinders must be hydrostatically tested every 5 years. During extended operations, empty air cylinders can be quickly replaced with fresh ones and then refilled from larger tanks in a cascade storage system or from an air compressor brought to the scene.
Positive versus negative pressure
Open circuit SCBAs use either "positive pressure" or "negative pressure" operation.
A negative pressure system relies on the internal pressure of the mask dropping to below the ambient pressure to activate flow. if the mask does not seal perfectly, some leakage of ambient gas into the mask will occur, which can be a problem with toxic or irritant smoke and fumes.
A positive pressure system slightly pressurises the interior of the mask and activates flow when the pressure difference is reduced, but still slightly above ambient. If the mask leaks, there will be continuous flow to maintain the pressure, and no inward leakage is possible. With a good fit this is economical on gas and prevents contamination. If the mask falls off the regulator will continuously expend gas trying to raise the pressure, and may consume a significant amount of gas before it is corrected.
Although the performance of both types of SCBA may be similar under optimum conditions, this "fail safe" behaviour makes a positive pressure SCBA preferable for most applications. As there is usually no air usage penalty in providing positive pressure, the negative pressure type is, in most cases, an obsolete configuration and is only seen with older equipment. However some users refuse to use this technology as in case of a damage or loss of the facepiece the air will be released uncontrolled. The leakage rate can be so high that a fully charged SCBA will be drained in less than three minutes, a problem that does not happen with negative pressure SCBA systems, which will simply allow the user to breathe the contaminated air leaking unto the facepiece instead of the air from the cylinder.
Masks
The fullface masks of breathing apparatus designed for use out of water are sometimes designed in a way that makes them unsuitable for scuba diving, although some may allow very shallow emergency submersion:
- The seal at the edge of the mask is a wide tube with thin, flexible walls running around the edge of the mask, full of air at atmospheric pressure. On the surface it pushes against the edges of the wearer's face, causing a tight seal despite small variations in head shape. At more than a few feet depth pressure (underwater or in a caisson) this tube collapses, destroying the seal and making the mask leak.
- Curved window which underwater would severely distort the image by refraction.
The mask can have a large viewport, or small eye lenses.
The mask might have a small orinasal breathing mask inside, reducing breathing deadspace.
The mask can also incorporate a two-way radio communicator.
Some early industrial rebreathers (e.g., the Siebe Gorman Proto) had a mouthpiece and attached noseclip instead of a mask.
Usage
There are two major application areas for SCBA: firefighting and industrial use. A third use now coming into practice is medical; for example, the American National Institutes of Health prescribe use of SCBAs for medical staff during treatment of ebola.
For firefighting, the design emphasis is on heat and flame resistance above cost. SCBAs designed for firefighting tend to be expensive because of the exotic materials used to provide the flame resistance, and to a lesser extent, to reduce the weight penalty on the firefighter. In addition, modern firefighting SCBAs incorporate a PASS device (personal alert safety system) or an ADSU (automatic distress signal unit) into their design. These units emit distinctive, high-pitched alarm tones to help locate firefighters in distress by automatically activating if movement is not sensed for a certain length of time (typically between 15 and 30 seconds), also allowing for manual activation should the need arise. In firefighting use, the layout of this breathing set should not interfere with ability to carry a rescued person over the firefighter's shoulders.
The other major application is for industrial users of various types. Historically, mining was an important area, and in Europe this is still reflected by limitations on use in the construction of SCBAs of metals that can cause sparks. Other important users are petrochemical, chemical, and nuclear industries. The design emphasis for industrial users depends on the precise application and extends from the bottom end which is cost critical, to the most severe environments where the SCBA is one part of an integrated protective environment which includes gas-tight suits for whole-body protection and ease of decontamination. Industrial users will often be supplied with air via an air line, and only carry compressed air for escape or decontamination purposes.
Temperature effect on pressure
The pressure gauge's indicated gas pressure changes with ambient temperature. As temperature decreases, the pressure inside the cylinder decreases. The relationship between the temperature and the pressure of a gas is defined by the formula PV = nRT. (See Universal gas constant.) The temperature is absolute, referenced to absolute zero, and may be in Kelvins, or Rankine.[3] The absolute change in temperature from 32 to 96 °F (0 to 36 °C) is by a factor of 1.13 (308.71 K/273.15 K). If an air cylinder is pressurized to 4,500 psi at 96 °F and later the temperature drops to 32 °F, the pressure gauge will indicate 4,000 psi (4,500/1.13). Stated differently, a drop in temperature of 10 °F (5.5 °C) causes a pressure decrease of about 82 psi (565 kPa). Failure to accurately account for the effect of temperature on pressure readings can result in underfilled air cylinders, which in turn could lead to a firefighter running out of air prematurely.
Regulation and standards
In the United States and Canada, SCBAs used in firefighting must meet guidelines established by the National Fire Protection Association, NFPA Standard 1981. If an SCBA is labeled as "1981 NFPA compliant", it is designed for firefighting. The current version of the standard was published in 2018.[4] These standards are revised every five years. Similarly, the National Institute for Occupational Safety and Health (NIOSH) has a certification program for SCBA that are intended to be used in chemical, biological, radiological, and nuclear (CBRN) environments.
Any SCBA supplied for use in Europe must comply with the requirements of the Personal Protective Equipment Directive (89/686/EEC). In practice this usually means that the SCBA must comply with the requirements of the European Standard EN 137:2006. This includes detailed requirements for the performance of the SCBA, the marking required, and the information to be provided to the user. Two classes of SCBA are recognised, Type 1 for industrial use and Type 2 for firefighting. Any SCBA conforming to this standard will have been verified to reliably operate and protect the user from -30 °C to +60 °C under a wide range of severe simulated operational conditions.
Examples
The Royal Australian Navy uses the open circuit compressed air breathing apparatus (OCCABA), a backpack-style, positive pressure breathing apparatus, for firefighting roles.
See also
- Glossary of firefighting terms – List of definitions of terms and jargon used in firefighting
- Oxygen mask – Interface between the oxygen delivery system and the human user
- Respirator – Device worn to protect the user from inhaling contaminants
- PASS device (personal alert safety system), also known as ADSU (automatic distress signal unit) – Device used to set off an alarm when a firefighter is in distress
- SCUBA – Self-contained underwater breathing apparatus
- Smoke hood, also known as Short Term Air Supply (STAS – Device to protect the user from smoke inhalation in an emergency}
- Jean-François Pilâtre de Rozier – French pioneer balloonist (1754–1785)
Notes
- IFSTA 2008, p. 190.
- IFSTA 2008, p. 191.
- Online Conversion – Temperature Conversion Archived 2016-02-19 at the Wayback Machine.
- "NFPA". NFPA. Archived from the original on 6 April 2018. Retrieved 5 May 2018.
References
- IFSTA (2008). Essentials of Fire Fighting and Fire Department Operations (5th ed.).
External links
- These references are related to NIOSH-certified SCBA with chemical, biological, radiological, and nuclear (CBRN) protection (SC/PD/CBRN):
- Rescuer Deaths in Underground Mines
- Literature
- Study of the physiological effects of wearing breathing apparatus Archived 2014-05-13 at the Wayback Machine by RG Love and others. Institute of Occupational Medicine Research Report TM/94/05